Telemetry advanced topics
If you have already created a temperature monitor and control module, your next project will be to create a power monitor, much like the ones we have at the elab.
You will be using a current transformer (CT) knowns as a Hawkeye 922 analog current sensor:
https://www.energycontrol.com/Veris-Hawkeye-H922
This device works with AC current on a single wire to convert AC current into a 0-5 Vdc voltage.
The Analog device you will use is one of these:
Unmigrated media: analog_um_v1.3.pdf (application/pdf, 2.9 MB)
Setup:
- follow the same steps you did with the temperature module to give your device an IP address (see the manual if you need help)
- connect the current sensor to the device, with (+) going to A0 (analog input 0) and (-) going to Agnd (analog ground)
- go to the web page for the device and notice that it should read 0 for the value of A0
- unclip the current sensor and clamp it around the single wire provided (we will be splitting a "pig tail" and connecting it to a hot water maker)
- turn on the hot water maker, and notice the value on the web page
- change the settings on the CT to the lowest value (0-30A) and notice the change
- in the manual, there are steps to calibrate the device, begin with the easy method: connect a Kill-a-Watt device to your little system and calibrate the analog device using the values you see there for power or current
- repeat with the harder method, using calculations in the manual, e.g. slope
- the reason we need to learn the harder method, is we may know voltage of a circuit that is too large or connected to measure current directly (unless we use sophisticated meters, next step)
- using a clamp-on current meter, calibrate the analog unit
- what do you notice about the similarity between the clamp on meter and the 922 unit?